ABB ACS150 - Options

Brake Choppers
The ACS150 is delivered with an additional brake chopper
as standard. No additional space or installation time
is required.
Brake Resistors
The brake resistor is selected using the respective
table.
|
Type Code |
Frame size |
Rmin
ohm |
Rmax
ohm |
PBRmax |
|
kW |
hp |
| 1
phase supply voltage 200 - 240 V units |
| ACS150-01X-02A4-2 |
R0 |
70 |
390 |
0.37 |
0.5 |
| ACS150-01X-04A7-2 |
R1 |
40 |
200 |
0.75 |
1 |
| ACS150-01X-06A7-2 |
R1 |
40 |
130 |
1.1 |
1.5 |
| ACS150-01X-07A5-2 |
R2 |
30 |
100 |
1.5 |
2 |
| ACS150-01X-09A8-2 |
R2 |
30 |
70 |
2.2 |
3 |
| 3
phase supply voltage 200-240 V units |
| ACS150-03X-02A4-2 |
R0 |
70 |
390 |
0.37 |
0.5 |
| ACS150-03X-03A5-2 |
R0 |
70 |
260 |
0.55 |
0.75 |
| ACS150-03X-04A7-2 |
R1 |
40 |
200 |
0.75 |
1 |
| ACS150-03X-06A7-2 |
R1 |
40 |
130 |
1.1 |
1.5 |
| ACS150-03X-07A5-2 |
R1 |
30 |
100 |
1.5 |
2 |
| ACS150-03X-09A8-2 |
R2 |
30 |
70 |
2.2 |
3 |
| 3
phase supply voltage 380 - 480 V units |
| ACS150-03X-01A2-4 |
R0 |
310 |
1180 |
0.37 |
0.5 |
| ACS150-03X-01A9-4 |
R0 |
230 |
800 |
0.55 |
0.75 |
| ACS150-03X-02A4-4 |
R0 |
210 |
500 |
0.75 |
1 |
| ACS150-03X-03A3-4 |
R1 |
150 |
400 |
1.1 |
1.5 |
| ACS150-03X-04A1-4 |
R1 |
130 |
300 |
1.5 |
2 |
| ACS150-03X-05A6-4 |
R1 |
100 |
200 |
2.2 |
3 |
| ACS150-03x-07A3-4 |
R1 |
70 |
150 |
3 |
4 |
| ACS150-03X-08A8-4 |
R1 |
70 |
110 |
4 |
5 |
ABB ACS150 Technical Data
Cooling
the ACS150 is fitted with cooling fans as standard.
The cooling air must be free from corrosive materials and
must not be above the maximum ambient temperature of 40oC
(50oC with derating).
Cooling Air Flow
|
Type Code |
Frame
size |
Heat
dissipation |
Air flow |
|
w |
BTU / Hr |
m3/h |
ft3/min |
| 1
phase supply voltage 200 - 240 V units |
| ACS150-01X-02A4-2 |
R0 |
25 |
85 |
-* |
-* |
| ACS150-01X-04A7-2 |
R1 |
46 |
157 |
24 |
14 |
| ACS150-01X-06A7-2 |
R1 |
71 |
242 |
24 |
14 |
| ACS150-01X-07A5-2 |
R2 |
73 |
249 |
21 |
12 |
| ACS150-01X-09A8-2 |
R2 |
96 |
328 |
21 |
12 |
| 3
phase supply voltage 200-240 V units |
| ACS150-03X-02A4-2 |
R0 |
19 |
65 |
-* |
-* |
| ACS150-03X-03A5-2 |
R0 |
31 |
106 |
-* |
-* |
| ACS150-03X-04A7-2 |
R1 |
38 |
130 |
24 |
14 |
| ACS150-03X-06A7-2 |
R1 |
60 |
205 |
24 |
14 |
| ACS150-03X-07A5-2 |
R1 |
62 |
212 |
21 |
12 |
| ACS150-03X-09A8-2 |
R2 |
83 |
283 |
21 |
12 |
| 3
phase supply voltage 380 - 480 V units |
| ACS150-03X-01A2-4 |
R0 |
11 |
38 |
-* |
-* |
| ACS150-03X-01A9-4 |
R0 |
11 |
55 |
-* |
-* |
| ACS150-03X-02A4-4 |
R0 |
21 |
72 |
-* |
-* |
| ACS150-03X-03A3-4 |
R1 |
31 |
106 |
13 |
8 |
| ACS150-03X-04A1-4 |
R1 |
40 |
137 |
13 |
8 |
| ACS150-03X-05A6-4 |
R1 |
61 |
208 |
19 |
11 |
| ACS150-03x-07A3-4 |
R1 |
74 |
253 |
24 |
14 |
| ACS150-03X-08A8-4 |
R1 |
94 |
321 |
24 |
14 |
Free Space Requirements
All frame sizes - 80mm space above, 80mm space below and
0mm space on left / right mm.
Fuses
Standard fuses can be used with ABB component drives.
For input fuse connections see selection table below:
|
Type code |
Frame size |
IEC Fuses |
UL Fuses |
|
A |
Fuse Type* |
A |
Fuse Type* |
| 1 phase supply
voltage 200 - 240 V units |
| ACS150-01X-02A4-2 |
R0 |
10 |
gG |
10 |
UL class T |
| ACS150-01X-04A7-2 |
R1 |
16 |
gG |
20 |
UL Class T |
| ACS150-01X-06A7-2 |
R1 |
20 |
gG |
25 |
UL Class T |
| ACS150-01X-07A5-2 |
R2 |
25 |
gG |
30 |
UL Class T |
| ACS150-01X-09A8-2 |
R2 |
35 |
gG |
35 |
UL Class T |
| 3 phase supply
voltage 200 - 240 V units |
| ACS150-03X-02A4-2 |
R0 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-04A4-2 |
R0 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-06A7-2 |
R1 |
10 |
gG |
15 |
UL Class T |
| ACS150-03X-06A7-2 |
R1 |
16 |
gG |
15 |
UL Class T |
| ACS150-03X-07A5-2 |
R1 |
16 |
gG |
15 |
UL Class T |
| ACS150-03X-09A8-2 |
R2 |
16 |
gG |
20 |
UL Class T |
| 3-phase supply
voltage 380 - 480 V units |
| ACS150-03X-01A2-4 |
R0 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-01A9-4 |
R0 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-02A4-4 |
R0 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-03A3-4 |
R1 |
10 |
gG |
10 |
UL Class T |
| ACS150-03X-04A1-4 |
R1 |
16 |
gG |
15 |
UL Class T |
| ACS150-03X-05A6-4 |
R1 |
16 |
gG |
15 |
UL Class T |
| ACS150-03X-07A3-4 |
R1 |
16 |
gG |
20 |
UL Class T |
| ACS150-03X-08A8-4 |
R1 |
20 |
gG |
25 |
UL Class T |
* According to IEC 60269 |