Click to send us a

|
|
|
ACS150 Technical Specification and Control Connections
Below is a technical specification of the ACS150.
| Mains Connection |
| Voltage and Power Range |
1 phase, 200 to 240V
± 10% |
| |
0.37 to 2.2 kW (0.5 to 3 hp) |
| |
3-phase, 200 to 240 V
± 10% |
| |
0.37 to 2.2 kW (0.5 to 3 hp) |
| |
3-phase, 380 to 480 V
± 10% |
| |
0.37 to 4kW (0.5 to 5 hp) |
| Frequency |
48 to 63Hz |
| Power factor |
0.98 |
| Motor Connection |
| Voltage |
3-phase, from 0 to Usupply |
| Frequency |
0 to 500 Hz |
| Continuous loading capability |
Rated output current I2N |
| (constant torque at a max. ambient
temperature 40oC) |
Overload capability
(at a max. ambient temperature of 40oC) |
At heavy duty use 1.5 x I2N
for 1 minute every 10 minutes
At start 1.8 x I2N
for 2 s |
Switching frequency
Default
Selectable |
4kHz
4 to 12 kHz with 4 kHz steps |
| Acceleration time |
0.1 to 1800 s |
| Deceleration time |
0.1 to 1800 s |
| Braking |
Inbuilt brake chopper as standard |
|
|
 |
| Environmental Limits |
| Ambient temperature |
-10 to 40oC
(14 to 104F), no frost allowed, 50oC
(122F) with 10% derating |
Altitude
Output current
|
Rated current available at 0 to
1000m
(0 to 3281 ft) reduced by 1% per 100m
(328 ft) over 1000 to 2000m (3281 to 6562 ft) |
| Relative humidity |
Lower than 95% (without
condensation) |
| Protection class |
IP20 / Optional NEMA 1 enclosure |
| Enclosure colour |
NCS 1502-Y, RAL 9002, PMS 420C |
| Contamination levels |
IEC721-3-3 |
| |
No conductive dust allowed |
| Transportation |
Class 1C2 (chemical gases) |
| |
Class 1S2 (solid particles) |
| Storage |
Class 2C2 (chemical gases) |
| |
Class 2S2 (solid particles) |
| Operation |
Class 3C2 (chemical gases) |
| |
Class 3S2 (solid particles) |
| Chokes |
| AC input chokes |
External option. |
| |
For reducing THD in partial loads and to comply
with EN61000-3-2. |
| AC output chokes |
External option.
To achieve longer motor cables. |
| Programmable
Control Connections |
| One analogue input |
|
| Voltage signal |
0 (2) to 10 V, Rin
> 312kΩ |
| Current signal |
0 (4) to 20 mA, Rin
= 100Ω |
| Resolution |
0.1% |
| Accuracy |
± 1% |
| Auxiliary Voltage |
24 V DC
± 10% |
| Five digital inputs |
12 to 24 V DC with internal or external supply,
PNP and NPN, pulse train 0 to 16kHz. |
| Input impedance |
2.4kΩ |
| One relay output |
|
| Type |
NO + NC |
| Maximum switching voltage |
250 V AC / 30 V DC |
| Maximum switching current |
0.5 A/30 V DC; 5 A/230 V AC |
| Maximum continuous current |
2 A rms |
| Product Compliance |
| Low voltage Directive 73/23/EEC with supplements |
| Machinery directive 98/37/EC |
| EMC Directive 89/336/EEC with supplements |
| Quality assurance system ISO 9001 |
| Environmental systems ISO 14001 |
| UL, cUL, CE, C-Tick, and GOST R approvals |
| EMC (according to
EN61800-3) |
| 2nd environmental filter, unrestricted
distribution with 30m (98ft) cable inbuilt as
standard |
|