ABB ACS550 Ratings, Types and Voltages
ACS550 - 01 - 03A3 - 4 + B055
Type Code
This is the unique reference number (shown above and in column 7) that clearly identifies your drive by power rating and frame size. Once you have selected the type code, the frame size (column 8) can be used to determine the drives dimensions.
Voltages
The ACS550 is available in two voltage ranges:
- 4 = 380 - 480 V
- 2 = 208 - 240 V
Insert either '4' or '2' depending on your chosen voltage, into the type code shown above.
Normal use vs heavy-duty use. For the majority of pump, fan and conveyor applications, select 'normal use' figures. For high overload requirements, select 'heavy-duty use' figures.
- Pn for kW = Typical motor power in 400 V at normal use
- Pn for hp = Typical motor power in 460 V at normal use
- Phd for kW = Typical motor power in 400 V at heavy-duty use
- Phd for hp = Typical motor power in 460 V at heavy-duty use
3-phase supply voltage 380-480 V Wall mounted units
|
Ratings |
Type code | Frame size | |||||
| Normal Use | Heavy duty use | ||||||
| Pn kW | Pn hp | I2n A | Phd kW | Phd hp | I2hd A | ||
| 1.1 | 1.5 | 3.3 | 0.75 | 1 | 2.4 | ACS550-01-03A3-4 | R1 |
| 1.5 | 2 | 4.1 | 1.1 | 1.5 | 3.3 | ACS550-01-04A1-4 | R1 |
| 2.2 | 3 | 5.4 | 1.5 | 2 | 4.1 | ACS550-01-05A4-4 | R1 |
| 3 | 3 | 6.9 | 2.2 | 3 | 5.4 | ACS550-01-06A9-4 | R1 |
| 4 | 5 | 8.8 | 3 | 3 | 6.9 | ACS550-01-08A8-4 | R1 |
| 5.5 | 7.5 | 11.9 | 4 | 5 | 8.8 | ACS550-01-012A-4 | R1 |
| 7.5 | 10 | 15.4 | 5.5 | 7.5 | 11.9 | ACS550-01-015A-4 | R2 |
| 11 | 15 | 23 | 7.5 | 10 | 15.4 | ACS550-01-023A-4 | R2 |
| 15 | 20 | 31 | 11 | 15 | 23 | ACS550-01-031A-4 | R3 |
| 18.5 | 25 | 38 | 15 | 20 | 31 | ACS550-01-038A-4 | R3 |
| 22 | 30 | 44 | 18.5 | 25 | 38 | ACS550-01-044A-4 | R4 |
| 30 | 40 | 59 | 22 | 30 | 44 | ACS550-01-059A-4 | R4 |
| 37 | 50 | 72 | 30 | 40 | 59 | ACS550-01-072A-4 | R4 |
| 45 | 75 | 96 | 37 | 60 | 77 | ACS550-01-096A-4 | R5 |
| 55 | 100 | 124 | 45 | 75 | 96 | ACS550-01-124A-4 | R6 |
| 75 | 125 | 157 | 55 | 100 | 124 | ACS550-01-157A-4 | R6 |
| 90 | 150 | 180 | 75 | 125 | 156 | ACS550-01-180A-4 | R6 |
| 110 | 150 | 195 | 90 | 125 | 162 | ACS550-01-195A-4 | R6 |
Free standing units |
|||||||
| 132 | 200 | 245 | 110 | 150 | 192 | ACS550-02-245A-4 | R7 |
| 160 | 200 | 289 | 132 | 200 | 224 | ACS550-02-289A-4 | R7 |
| 200 | 300 | 368 | 160 | 250 | 302 | ACS550-02-368A-4 | R8 |
| 250 | 400 | 486 | 200 | 350 | 414 | ACS550-02-486A-4 | R8 |
| 280 | 450 | 526 | 250 | 400 | 477 | ACS550-02-526A-4 | R8 |
| 315 | 500 | 602 | 280 | 450 | 515 | ACS550-02-602A-4 | R8 |
| 355 | 500 | 645 | 315 | 500 | 590 | ACS550-02-645A-4 | R8 |
3-phase supply voltage 208-240 V. Wall mounted units |
|||||||
|
Ratings |
Type code | Frame size | |||||
| Normal Use | Heavy duty use | ||||||
| Pn kW | Pn hp | I2n A | Phd kW | Phd hp | I2hd A | ||
| 1.1 | 1.0 | 4.6 | 0.75 | 0.8 | 3.5 | ACS550-01-04A6-2 | R1 |
| 1.5 | 1.5 | 6.6 | 1.1 | 1.0 | 4.6 | ACS550-01-06A6-2 | R1 |
| 2.2 | 2.0 | 7.5 | 1.5 | 1.5 | 6.6 | ACS550-01-07A5-2 | R1 |
| 3.0 | 3.0 | 11.8 | 2.2 | 2.0 | 7.5 | ACS550-01-012A-2 | R1 |
| 4.0 | 5.0 | 16.7 | 3.0 | 3.0 | 11.8 | ACS550-01-017A-2 | R1 |
| 5.5 | 7.5 | 24.2 | 4.0 | 5.0 | 16.7 | ACS550-01-024A-2 | R2 |
| 7.5 | 10.0 | 30.8 | 5.5 | 7.5 | 24.2 | ACS550-01-031A-2 | R2 |
| 11.0 | 15.0 | 46.2 | 7.5 | 10.0 | 30.8 | ACS550-01-046A-2 | R3 |
| 15.0 | 20.0 | 59.4 | 11.0 | 15.0 | 46.2 | ACS550-01-059A-2 | R3 |
| 18.5 | 25.0 | 74.8 | 15.0 | 20.0 | 59.4 | ACS550-01-075A-2 | R4 |
| 22.0 | 30.0 | 88.0 | 18.5 | 25.0 | 74.8 | ACS550-01-088A-2 | R4 |
| 30.0 | 40.0 | 114 | 22.0 | 30.0 | 88.0 | ACS550-01-114A-2 | R4 |
| 37.0 | 50.0 | 143 | 30.0 | 40 | 114 | ACS550-01-143A-2 | R6 |
| 45.0 | 60.0 | 178 | 37.0 | 50 | 150 | ACS550-01-178A-2 | R6 |
| 55.0 | 75.0 | 221 | 45.0 | 60 | 178 | ACS550-01-221A-2 | R6 |
| 75.0 | 100 | 248 | 55.0 | 75 | 192 | ACS550-01-248A-2 | R6 |