Plug in External Options
DriveWindow Light Software
This PC software is used for rapid commissioning and controlling
of drives. It has features for programming, monitoring,
trouble shooting and maintenance. it is also a setup and
control tool which is Win98, WinNT, Win2000 and WinXP compatible.
DriveWindow Light 2 operates both off and on-line. No
additional PC hardware is required. It uses the PC's RS-232
port. It is compatible with drive types ACS140, ACS160,
ACS400, ACS550, ACS600, ACS800 and DCS400. Features include:
- Graphical start-up wizards
- Off and on-line viewing and changing of drive parameters
- Backup and restore parameters. In a fault situation
the parameters can be reloaded resulting in time savings.
- Graphical monitoring of actual signal values
- I/O mapping table
- Control of the drive
Output Chokes
Output chokes are used when motor cables above normal length are
required. Cable can be roughly 1.5 times standard cable
length, see below. The maximum switching frequency with output
chokes is 4 kHz.
Selection Table
| Type Code |
Max. cable mm2 |
I A |
Max cable length with
coke (m) |
Max cable length
without coke (m) |
Output choke type code |
| ACS550-01-03A3-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-04A1-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-05A4-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-06A9-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-08A8-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-12A-4 |
10 |
15 |
150 |
100 |
NOCH-0016-6X |
| ACS550-01-015A-4 |
10 |
15 |
250 |
200 |
NOCH-0016-6X |
| ACS550-01-023A-4 |
10 |
15 |
250 |
200 |
NOCH-0030-6X |
| ACS550-01-031A-4 |
16 |
28 |
250 |
200 |
NOCH-0030-6X |
| ACS550-01-038A-4 |
16 |
28 |
250 |
200 |
NOCH-0030-6X |
| ACS550-01-044A-4 |
35 |
65 |
300 |
200 |
NOCH-0070-6X |
| ACS550-01-059A-4 |
35 |
65 |
300 |
200 |
NOCH-0070-6X |
| ACS550-01-072A-4 |
35 |
65 |
300 |
200 |
NOCH-0070-6X |
Dimensions
Output choke
Type code |
A
mm |
B
mm |
C
mm |
Weight |
| NOCH-0016-62/65 |
199 |
323 |
154 |
6 |
| NOCH-0030-62/65 |
249 |
348 |
172 |
9 |
| NOCH-0070-62/65 |
279 |
433 |
202 |
15.5 |
|
|
 |
Note : An output choke does not improve the EMC performance of
the drive. To fulfil local EMC requirements use sufficient RFI
filtering.
Brake Units and Choppers
Frame sizes R1 and R2 are delivered with integrated rake
choppers as standard. Other units can use the
compact-sized brake units which include brake chopper and
resistor. For more information please refer to the
ACS-BRK brake units installation and start up guide.
| Frequency
converter input voltage |
resistor ohm |
Continuous
output W |
Max output
20 s W |
Brake unit
type code |
200 - 240 V AC
380-480 V AC |
32 |
2000 |
4500
12000 |
ACS-BRK-C |
200 - 240 V AC
380 - 480 V AC |
10.5 |
7000 |
14000
42000 |
ACS-BRK-D |
|
|
 |
Dimensions
| Width (W) mm |
Height (H) mm |
Depth (D) mm |
Weight kg |
Brake Unit Type Code |
| 150 |
500 |
347 |
7.5 |
ACS-BRK-C |
| 270 |
600 |
450 |
20.5 |
ACS-BRK-D |
|