| Conductor |
|
| Number of pairs : |
1 |
| Total number of conductors : |
2 |
| AWG : |
16 |
| Stranding |
19 x 29 |
| Conductor Material |
TC - Tinned Copper |
| |
|
| Insulation |
|
| Insulation material : |
PVC - Polyvinyl Chloride |
| Non insulation wall thickness |
0.023" |
| Lay length |
2" |
| Twists / ft. |
6 |
| |
|
| Pair Colour Code Chart |
|
| Number |
Colour |
| 1 |
Black and White |
| |
|
| Inner shield material : |
Unshielded |
| Outer shield material : |
Unshielded |
| Outer jacket material : |
Unshielded |
| Outer jacket nominal wall thickness : |
0.32" |
| Overall nominal diameter : |
.274" |
| |
|
| Mechanical Characteristics |
|
| Operating temperature range : |
-20oC to +80oC |
| Non-UL temperature rating : |
60oC (UL AWM
Style 2598) |
| Bulk cable weight : |
35.9lbs / 1000ft |
| Max recommended pulling tension : |
61 lbs |
| Minimum bending radius (install) : |
5.1" |
| |
|
| Applicable Standards |
|
| NEC / (UL) Specification |
CMG |
| CEC / C (UL) Specification |
CMG |
| AWM Specification |
UL Style 2598 (300 V 60oC |
| EU CE Mark (Y/N) |
Yes |
| EU RoHS Compliant (Y/N) |
Yes |
| EU RoHS Compliance Date |
04/01/2005 |
| UL Flame Test : |
UL1685 FT4 Loading |
| C(UL) Flame Test : |
FT4 |
| Plenum : |
No |
| |
|
| Electrical Characteristics |
|
| Nom Inductance : |
0.184 μH/ft |
| Nom. Capacitance Conductor to Conductor @ 1 KHz : |
33pF/ft |
| Nom. Conductor DC Resistance @ 20 Deg C : |
4.49 Ohms / 1000 ft |
| Max Operating Voltage - UL : |
300 V RMS (UL AWM Style 2598) |
| Max. recommended current : |
7.1 Amps per conductor @25oC |
| |
|
| Notes |
Nominal Breakdown Voltage - Jacket 20 KV RMS; Nominal
Breakdown Voltage
Between Conductors 20 KV RMS. |