Pyrolyon® Cable
A fire resistant, fire retardant and low smoke cable for use in
buildings where systems need to remain operational.
|
|
CSE holds stock of a wide range of cables -
Contact Corrina
CSE's cable consultant |
Application :
- Fire detection and alarm systems
- Public address systems
- Emergency lighting
Design :
- Conductor : Bare copper, Solid Class 1 (1, 1.5mm2),
Stranded Class 2 (2.5 4mm2) on request solid class 1 according to BS
6360 / IEC 60228
- Insulation : Silicon rubber to BS 7655
- Un-insulated protective conductor : Tinned copper
according to BS6360 same class and cross sectional area as insulated
conductor. On multicore cables (≥ 7
cores) - drain wire 0.5mm2
- Tape : Aluminium/polyester tape with optional polyester
tape
- Outer sheath : Halogen free polyolefin. colour : red,
white or black.
|
|
 |
Marking :
n x s BS 7629-1 BS 6387 CWZ
BS 5939-1 Standard
Pyrolyon E BASEC 205
Factory number CE
Core identification :
2 cores : brown blue
3 cores : brown black grey
4 cores : brown black grey blue
Standards :
BS 7629 Part 1
BS 6387 CWZ
BS 5839-1 : 2002 Cat. Standard
Electrical characteristics
Rated Voltage Uo/U 300 / 500 V
Usage characteristics
Gases toxicity BS 6425, IEC 60754, EN 50267
Fire resistant BS 6387 CWZ, IEC 60331, EN 50200 PH 30, BS 8434-1
Fire retardant BS 4066 Part 3 & 1, IEC 60332 Part 3 & 1, EN 50265 1 &
2.1
Smoke density BS 7622, IEC 61034, EN 50268
Halogen free : BS 6425, EN 50267, IEC 60754
Low toxicity : BS 6425, EN 50267, IEC 60754
Low corrosivity : BS 6425, EN 50267; IEC 60754
Temperature : -20 + 60 oC |