About Us  Contact Us  Blog!  Home
CSE Industrial Electrical Distributors CSE Head Office
CSE Head Office :
01628 529448
CSE Southampton
CSE Southampton :
023 8063 3055
CSE Cables
CSE Cables :
01628 850024
ABB Drives Motor Control Gear Circuit Protection Switch Gear Special Offers Cable Industrial Controls
Danfoss Drives Cable Management Control Products Accessories Power Distribution Enclosures Buy On-Line
ABB MCB's
Distribution Boards
RCD / RCB's
ABB Modular Devices
REM Live

Click to send us a

 

 

ABB System proM - Residual Current Devices (RCD's)

BSEN 61008 ratings 16 to 100A.

Description

ABB residual current devices have a measuring system consisting of a summation transformer with a permanent magnet tripping device, operating without the need of an auxilliary supply, to open a circuit automatically it an earth leakage fault occurs between phase and earth greater or equal to its rated sensitivity in mA.

Provision of earth leakage, switching and isolation functionality to electrical circuits.

Same form and design as the S2 MCB range, allowign easy interconnection with busbar blocks and common mounting in distribution panels.

Suitable for symmetrical DIN rail or panel mounting.

Technical Data

  • Specification to BS EN 61008: F360, F660 Class AC, F370 and F390 Class A
  • Rated voltage : Two pole 230V AC, Four pole 230 / 400V AC.
  • Maximum operating voltage : Rated voltage +10%
  • Test button range: 100V AC up to 264V AC
  • Frequency: 50 to 60Hz
  • Cable capacity: 25mm2 up to 63A, 50mm2 for 80 and 100A
  • Life expectancy: at least 5,000 operations
  • Maximum tightening torque: 3Nm
  • Ambient temperature: -25oC to +55oC
  • Maximum weights : 2 pole 0.365kg, 4 pole 0.49kg

Two Pole F362 & F662. Class AC

Current (A) 10mA 30mA Sensitivity 100mA 300mA
16 F362-16/0.01 - - -
25 - F362-25/0.03 F362-25/0.1 F362-25/0.3
40 - F362-40/0.03 F362-40/0.1 F362-40/0.3
63 - F362-63/0.03 F362-63/0.1 F362-63/0.3
80 - F662-80/0.03 F662-80/0.1 F662-80/0.3
100 - F662-100/0.03 F662-100/0.1 F662-100/0.3


Four Pole F364 & F664, Class AC.

Current (A) 30mA Sensitivity 100mA 300mA
25 F364-25/0.03 F364-25/0.1 F364-25/0.3
40 F364-40/0.03 F364-40/0.1 F364-40/0.3
63 F364-63/0.03 F364-63/0.1 F364-63/0.3
80 F664-80/0.03 F664-80/0.1 F664-80/0.3
100 F664-100/0.03 F664-100/0.1 F664-100/0.3


Two Pole F372 & F392, Class A (pulsating DC sensitive)

Current (A) 30mA Sensitivity 100mA 300mA
25 F372-25/0.03 F372-25/0.1 F372-25/0.3
40 F372-40/0.03 F372-40/0.1 F372-40/0.3
63 F372-63/0.03 F372-63/0.1 F372-63/0.3
63 time delayed - - F392-63/0.3


Four Pole F374 & F394, Class A (pulsating DC sensitive)

Current (A) 30mA Sensitivity 100mA 300mA
25 F374-25/0.03 F374-25/0.1 F374-25/0.3
40 F374-40/0.03 F374-40/0.1 F374-40/0.3
63 F374-63/0.03 F374-63/0.1 F374-63/0.3
63 time delayed - F394-63/0.1 F394-63/0.3
     
   

CSE Industrial Electrical Distributors; Email : - UK Tel:01628 529448; UK Fax:01628 810093;
Cable Enquiries Tel
: 01628 850024; Email :

Tel : International enquiries +44 (0)1628 529448, International Fax - +44 (0)1628 810093 , Tel : South UK - 0870 777 3205