The Micro contains fully encapsulated, triple redundant, electronic
circuits and the connection is via a flying lead which connects to the
electrical supply as close as possible to the Isolation point - i.e.
immediately after the disconnect switch.
VISUAL SAFETY WARNING and VERIFICATION of
ISOLATION REM Live
Micro Installation Data Sheet
|
|||||||||||||||||||||||||
|
Supply Details
|
Connection Details Black - L1 |
|||||||||||||||||
Current, AC or DC, 5 mA (Maximum – voltage dependent)
Connect REMLIVE to the OUTGOING side of the Isolator / Circuit Breaker,
making sure that the connections are Electrically and Mechanically sound
and in accordance with current regulations for electrical installations.
If the Isolator / Circuit Breaker is rated at more than 200 Amps, or the
REMLIVE unit is mounted outside the fault free zone, connect via
suitable fuses complying with current electrical regulations for
electrical installations.
WARNING ! DO NOT FIT REMLIVE IF THE UNIT IS DAMAGED IN ANY WA
REPLACE the REMLIVE unit if EITHER of the two sets of THREE FLASHING INDICATORS FAIL TO FLASH approximately every 1.5 SECONDS, when a live supply is connected. If uncertain about any application or aspect of fitting or operating REMLIVE, contact the supplier.
On 3 Phase installations
the Neutral & Earth connections are Optional, however should two phases
fail, the indicators will cease to operate if Neutral or Earth is NOT
USED. Remlive Limited strongly recommend the use of both NEUTRAL & EARTH
connections to ensure 100% availability of the Remlive Warning
Indicator. If a Neutral connection is not available , the Neutral
connection can be connected to earth, however, advise from a qualified
electrical engineer should be taken before connecting in this way. Using
Neutral and earth connections has the added benefit of indicting a
voltage above 24volts is present – Neutral to Earth – even when all
phase voltages are at zero
| In any event Remember!! |
LIVE EQUIPMENT CAN KILL. OTHER SAFETY PROCEDURES STILL APPLY. TEST BEFORE TOUCHING. |
To mechanically install Micro-Remlive simply drill or punch a 30mm
hole with locating hole, as per a standard pushbutton.
Place Micro-Remlive in the hole, viewed from the front, and thread the
locking nut along the cable. With the two small handles and locking
tooth, slide along the ratchet until firmly secure. Using a screwdriver,
push the locking tooth one final notch for best results. To release,
rotate the handles through 90 degrees and slide locking nut off.
REMLIVE is manufactured using modern manufacturing techniques and top quality materials. It has undergone ALL the rigorous tests necessary for it to attain the CE Mark and to ensure that it conforms with the essential protection requirements of EC Directive 89/336/EEC relating to ELECTROMAGNETIC COMPATIBILTY by the application of the following standards: EN 50081 – 2 Emissions. EN 50082 – 2 Immunity.
REMLIVE also conforms with the essential protection requirements of EC Directive 73/23/EEC relating to the safety of electrical equipment by the application of the following standards: EN 61010 Low Voltage Directive.
Micro-REMLIVE is housed in a robust VO Rated special enclosure, which has been selected for its durability and protective, insulation and zero halogen properties. Micro-REMLIVE has been designed to give protection to IP65 and should ALWAYS be fitted in a accordance with the manufacturer’s recommendations.
The following sequences are related to the illumination and
connection of the Micro-Remlive - uRL-1 VISUAL SAFETY WARNING and
VERIFICATION of ISOLATION DEVICE
The Four Light Emitting Diodes outer most from the centre above L1& L2,
below L3 & N, will flash approximately every 1.5 seconds if Micro-Remlive
detects a potential difference above
24Vac / 24Vdc between any two connected cables.
|