| FC 301 A1* | FC301 | FC302 | |
| Power range 200 -240 V [kW] | 0.25-1.5 | 0.25-45 | 0.37 - 45 |
| Power range 380- (480) 500 [kW] | 0.37 - 1.5 | 0.37 - 45 | 0.37 - 1.1 M |
| Power range 550 -600 V [kWI | - | - | 0.75 - 7.5 |
| Power range 525 -690 V [kWI | - | - | 11-1.2 M |
| Amb. temp'C Avg.24 hours (IP 21) w/o de-rating | 45 | 45 | 45 |
| Ambient temp'C max (IP21) w/o de-rating | 50 | 50 | 50 |
| Ambient temp'C max with de-rating | 55 | 55 | 55 |
| IP 21/NEMA typel/1P 5SINEMA type12 | |||
| IP66/NEMAtype4x | - | ||
| Smart Logic Control | |||
| Logic Rule Control | |||
| Safe Stop input function approved | - | ||
| Local Control Panel numerical or graphical | |||
| Info/Help function Personal menu (macro) | |||
| Regional settings (US mode) | |||
| Language settings | |||
| Change made restore previous setting | |||
| Password protection | |||
| Analogue input | 0 to +10V | 0 to +10V | -10 to +10V |
| Digital inputs | 5 | 5 | 6 |
| Digital transistor outputs '1 | 1 | 1 | |
| Relay outputs | 1 | 1 | 2 |
| Analogue output resolution | 12 bit | 12 bit | 12 bit |
| PC connection: RS 485 and USB | |||
| Default motor data | |||
| Permanent Magnet Motor algorithm | - | - | |
| Process PID control | |||
| Precise Start/Stop | |||
| Preset references | 8 | 8 | 8 |
| Digipotmeter | |||
| Ramp functions: linear and S-ramps | |||
| Profibus, DeviceNet, CANOpen | |||
| ProfiSafe | - | - | |
| Interface options: | |||
| Extended input/outputs MCB 101 | |||
| Encoders option MCB 102 | |||
| Resolver option MCB 103 | |||
| Relay option MCB 1OS | |||
| Safe PLC interface MCB 108 | - | ||
| Motion Control Options: MCO 305 | - | ||
| External 24 Vback-up option MCB 107 | - | ||
| Cable length -screened/unscreened | 25/50m | 50/75m | 150/300 m |
| RFI EN55011 cI A2 (Industry) | <5 m | <5m | <5m |
| RFI EN55011 cI Al (Industry) | <25 M | <50m | <150 m |
| RFI EN55011 cI B(Domestic) | 2.5 m | <10 m | <50 m |
| Voltage Vector Control WC+ | |||
| FluxVector Control | - | - | |
| Automatic Energy Optimizing (AOE) | - | - | |
| Controlled ramp down | - | - | |
| Flying start -catch spinning motor | |||
| Variable switching frequency 1 -16 kHz 2) | |||
| Over Voltage Control | |||
| Fan replaceable |
*Smallest cabinet size
1. Converting digital inputs
2. Power size dependent