| Mains Supply (L1, L2,
L3) |
| Supply voltage 200-240 V units |
3 x 200/208/220/230/240 V ±10% |
| Supply voltage 380-500 V units |
3 x 380/400/415/440/460/500 V
±10% |
| Supply voltage 525-600 V |
3 x 525 / 550/575/600 V ±10% |
| Supply Frequency: |
|
| Max imbalance of supply voltage : |
48-62 Hz =/- 1% |
| True Power factor (l) |
0.90 nominal at rated load |
| Displacement Power Factor (cos f) |
near unity (>0.98) |
| No. of switchings on supply input L1, L2, L3 |
approx. 1 time / min. |
| VLT Output data (U, V,
W): |
| Outpu voltage |
0-100% of supply voltage |
| Output frequency |
0-1000 Hz |
| Rated motor voltage, 200-240 V units |
200 / 208 / 220 / 230 / 240 V |
| Rated motor voltage 380 - 500 V units |
380 / 400 / 415 / 440 / 460 / 480 / 500 V |
| Rated motor voltage 525 - 600 V units |
525 / 550 / 575 V |
| Rated motor frequency |
Unlimited |
| Ramp times |
0.05 - 3600 sec. |
| Control Card, Digital
Inputs |
| Number of programmable digital inputs |
8 |
| Terminal nos |
16, 17, 18, 19, 27, 29, 32, 33 |
| Voltage level |
0-24 V DC (PNP positive logics) |
| Voltage level, logical '0' |
<5 V DC |
| Voltage level, logical '1' |
>10 V DC |
| Maximum voltage on input |
28 V DC |
| Input resistance, Ri |
2kΩ |
| Scanning time per input |
3 msec. |
| Reliable galvanic isolation : all digital
inputs are galvanically isolated from the supply voltage (PELV).
In addition, the digital inputs can be isolated from the
other terminals on the control card by connecting an
external 24V DC supply and opening switch 4. VLT 5001
- 5250, 525 - 600V do not meet PELV. |
| Control card, analogue
inputs |
| No. of programmable analogue voltage inputs / thermistor
inputs |
2 |
| Terminal nos |
53,54 |
| Voltage level |
0 - ±10 V DC
(scalable) |
| Input resistance Ri |
10kΩ |
| No. of programmable analogue current inputs |
1 |
| Terminal no. |
60 |
| Current range |
0/4 - ±20mA
(scalable) |
| Input resistance, Ri |
200 Ω |
| Resolution |
10 bit + sign |
| Accuracy on input |
Max. error 1% of full scale |
| Scanning time per input |
3 msec |
| Terminal no. ground |
55 |
| Reliable galvanic isolation : All analogue
inputs are galvanically isolated from the supply voltage (PELV)
* as well as other inputs and outputs. *VLT 5001 - 5250,
525-600 V do not meet PELV |
| Control card, pulse /
encoder input: |
| No. of programmable pulse encoder inputs |
4 |
| Terminal nos |
17, 29, 32, 33 |
| Max. frequency on terminal 17 |
5 kHz |
| Max. frequency on terminals 29, 32, 33 |
20 kHz (PNP open collector) |
| Max. frequency on terminals 29, 32, 33 |
65 kHz (push-pull) |
| Voltage level |
0-24 V DC (PNP positive logics) |
| Voltage level, logical '0' |
< 5 V DC |
| Voltage level, logical '1' |
>10 V DC |
| Maximum voltage on input |
28 V DC |
| Input resistance, Ri |
2 kΩ |
| Scanning time per input |
3 msec |
| Resolution |
10 bit + sign |
| Accuracy (100 - 1 kHz), terminals 17, 29, 33 |
Max. error : 0.5% of full scale |
| Accuracy (1 - 5 kHz), terminal 17 |
Max. error: 0.1% of full scale |
| Accuracy (1-65 kHz), terminals 29, 33 |
Max. error : 0.1% of full scale |
| Reliable galvanic isolation : All pulse /
encoder inputs are galvanically isolated from the supply
voltage (PELV)*). In addition, pulse and encoder
inputs can be isolated from the other terminals on the
control card by connecting an external 24 V DC supply and
opening switch 4. * VLT 5001-5250, 525-600 V do not
meet PELV. |
| Control Card, digital /
pulse and analogue outputs: |
| No. of programmable digital and analogue outputs. |
2 |
| Terminal nos |
42, 45 |
| Voltage level at digital / pulse output |
0 - 24 V DC |
| Minimum load to ground (terminal 39) at digital pulse
output |
600 Ω |
| Frequency ranges (digital output used as pulse output) |
0-32 kHz |
| Current range at analogue output |
0/4 - 20 mA |
| Maximum load to ground (terminal 39) at analgoue output |
500 Ω |
| Accuracy of analogue output |
Max. error : 1.5% of full scale |
| Resolution on analogue output |
8 bit |
| Reliable galvanic isolation : all digital
and analogue outputs are galvanically isolated from the
supply voltage (PELV)*, as well as other inputs and outputs.
* VLT 5001-5250, 525 - 600 V do not meet PELV. |
| Control Card, 24 V DC
supply |
| Terminal nos |
12, 13 |
| Max. load (short circuit protection) |
200 mA |
| Terminal nos. ground |
20, 39 |
| Reliable galvanic isolation : The 24 V DC
supply is galvanically isolated from the supply voltage (PELV)*,
but has the same potential as the analogue outputs.* |
| Control card, RS 485
serial communication |
| Terminal nos |
68 (TX+, RX+), 69 (TX-, RX-) |
| Reliable galvanic isolation : full galvanic
isolation |
| Relay outputs: |
| No. of programmable relay outputs |
2 |
| Terminal nos., control card |
4-5 (make) |
| Max. terminal load (AC) on 4-5, control card |
50 V AC, 1 A 60 VA |
| Max. terminal load (DC) on 4-5, control card |
75 V DC, 0.1 A, 30 W |
| Max. terminal load (DC) on 4-5, control card for UL /
cUL applications |
30 V AC, 1 A / 42.5 V DC, 1A |
| Terminal nos., power card |
1-3 (break), 1-2 (make) |
| Max. terminal load (AC) on 1-3, 1-2, power card |
240 V AC, 2 A, 60 VA |
| Max. terminal load on 1-3, 1-2 , power card |
50 V DC, 2 A |
| Min terminal load on 1-3, 1-2, power card |
24 V DC 10 mA, 24 V AC 100 mA |
| Brake Resistor
terminals (only SB, EB, DE and PB units): |
| Terminal nos |
81,82 |
| External 24 Volt DC
supply |
| Terminal nos |
35,36 |
| Voltage range |
24 V DC ±15% (max.
37 V DC for 10 sec) |
| Max. voltage ripple |
2 V DC |
| Power consumption |
15 W - 50 W (50 W for start-up, 20 msec.) |
| Min. pre-fuse |
6 Amp |
| Reliable galvanic isolation : full galvanic
isolation if the external 24 V DC supply is also of the PELV
type. |
| Cable lengths,
cross-sections and connectors |
| Max. motor cable length, screened cable |
150m |
| Max. motor cable length, unscreened cable |
300m |
| Max. motor cable length, screened cable VLT 5011 380 -
500 V |
100m |
Max. motor cable length, screened cable VLT 5011 525 -
600 V
and VLT 5008, normal overload mode, 525 - 600 V |
50m |
| Max. brake cable length, screened cable |
20m |
| Max. loadsharing cable length screened cable |
25m from frequency converter to DC bar. |
| Max. cable cross-section for 24 V external DC supply -
VLT 5001 - 5027, 200 - 240 V; VLT 5001 - 5102 380-500 V; VLT
5001-5062 525-600V |
4mm2 / 10 AWG |
| VLT 5032-5052 200-240 V; VLT 5122-5500 380-500 V; VLT
5075-5250 525-600 V |
2.5mm2 / 12 AWG |
| Max. cross-section for control cables |
1.5mm2 / 16 AWG |
| Max. cross-section for serial communication |
1.5mm2 / 16 AWG |
| If UL / cUL is to be complied with, cable
with temperature class 60/75oC
must be used (VLT 5001 - 5062 380 - 500 V, 525 - 600 V and
VLT 5001 - 5027 200 - 240 V). If UL / cUL is to be
complied with, cable with temperature class 75oC must be
used (VLT 5072 - 5500 380 - 500 V, VLT 5032 - 5052 200 - 240
V, VLT 5075 - 5250 525 - 600 V). Connectors are for
use of both copper and aluminium cables, unless other is
specified. |