ABB Manual Motor Starter MS132

ABB Manual Motor Starter MS132

With Thermal and Electromagnetic Protection

Application

  • Short Circuit Protection
  • Overload Protection
  • Trip class 10
  • Phase loss sensitivity
  • ON/OFF switching functionality
  • Disconnecting feature
  • Suitable for three-and single phase applications

Description

  • 45 mm width
  • Lockable handle
  • Clear position of hte handle ON/OFF/TRIP
  • Magnetic tripping optically signalled in the front
  • One range of common accessories for MS116 & MS132

Ordering Details

Rated Power
400 V AC-3
Setting Ranges Type Order Code Short-Circuit breaking Ics
at 400 V AC
Rated Instantaneous
short circuit current setting
kW A ... A     kA A
0.03 0.10 ... 0.16 MS132-0.16 1SAM 350 000 R1001 100 1.25 ... 1.87
0.06 0.16 ... 0.25 MS132-0.25 1SAM 350 000 R1002 100 1.95 ... 2.92
0.09 0.25 ... 0.40 MS132-0.4 1SAM 350 000 R1003 100 3.12 ... 4.68
0.12 0.40 ... 0.63 MS132-0.63 1SAM 350 000 R1004 100 4.91 ... 7.37
0.25 0.63 ... 1.00 MS132-1.0 1SAM 350 000 R1005 100 9.20 ... 13.8
0.55 1.00 ... 1.60 MS132-1.6 1SAM 350 000 R1006 100 14.7 ... 22.1
0.75 1.60 ... 2.50 MS132-2.5 1SAM 350 000 R1007 100 23.0 ... 34.5
1.5 2.50 ... 4.00 MS132-4.0 1SAM 350 000 R1008 100 40.0 ... 60.0
2.2 4.00 ... 6.30 MS132-6.3 1SAM 350 000 R1009 100 63.0 ... 94.5
4 6.30 ... 10.0 MS132-10 1SAM 350 000 R1010 100 120 ... 180
5.5 8.00 ... 12.0 MS132-12 1SAM 350 000 R1012 100 144 ... 216
7.5 10.0 ... 16.0 MS132-16 1SAM 350 000 R1011 100 192 ... 288
9 16.0 ... 20.0 MS132-20 1SAM 350 000 R1013 100 240 ... 360
12.5 20.0 ... 25.0 MS132-25 1SAM 350 000 R1014 50 300 ... 450
15 25.0 ... 32.0 MS132-32 1SAM 350 000 R1015 25 384 ... 576

Technical Data

  MS132  
Manual Motor Starter Types up to 10 A up to 16 A up to 32 A
Standards Conformity to standards       IEC/EN60947-1, IEC/EN60947-4-1, UL 508, CSA C22.2 No. 14
  Phase loss sensitivity (acc. to IEC/EN 60947-4-1) Yes    
  Disconnecting feature (acc. to IEC/EN 60947-2) Yes    
General Data Mounting Position       Position 1-6    
  Degree of protection (acc. to IEC 60947-1) IP 20    
  Mechancial durability       100000 cycles    
  Electrical durability       50000 cycles    
  Utilisation category       A    
IEC Main Circuit Rated operational voltage Ue   AC 690 V AC    
  (acc. to IEC / EN 60947-1)   DC 250 V DC    
  Rated operational current Ie     up to 10 A up to 16 A up to 32 A
  Rated operational current DC-5 Ie          
  3 conducting paths in series up to 250 V     see"rated operational current"
  Rated service short-circuit breaking capacity DC Ics 10 kA    
  3 conducting paths in series up to 250 V          
  Rated frequency       DC, 50 / 60 Hz    
  Trip class       10 (10A for MS132-0.16) 10 10
Isolation Data Rated impulse withstand voltage Uimp     6 kV    
(acc. to IEC/EN 60947-1) Rated insulation Ui       690 V    
Environmental data Ambient air temperature            
  Operation Open - compensated -25 ... +60 oC    
    Open     -25 ... + 70oC    
    Enclosed (IB132)     0 ... +40oC    
  Storage       -50 ... +80oC    
  Vibration (acc. to IEC/EN 60068-2-6) 5g / 3-150 Hz    
  Shock (acc. to IEC/EN 60068-2-27) 25 g / 11ms    
Connecting Capacity Rigid 1 or 2 x 1 ... 4 mm2 1 ... 4 mm2 2.5 ... 6 mm2
  Flexible with ferrule 1 or 2 x 0.72 ... 2.5mm2 0.75 ... 2.5mm2 1 ... 6 mm2
  Flexible without ferrule 1 or 2 x 0.75 ... 2.5mm2 0.75 ... 2.5mm2 1 ... 6 mm2
  Stripping Length       9mm 10mm 10mm
  Tightening Torque       0.8 ... 1.2 Nm 1.5 Nm 2.0 Nm
UL/CSA              
Main Circuit Max. Operational Voltage       600 V AC    
  Short Circuit Rating 480 V AC     30 kA    
    600 V AC     18 kA    
Connecting Capacity Stranded 1 or 2 x AWG 16 ... 12 AWG 16 ... 12 AWG 12 ... 8
Flexible with ferrule 1 or 2 x AWG 16 ... 12 AWG 16 ... 12 AWG 12 ... 8
  Stripping length       9mm 10mm 10mm
  Tightening torque       10 ... 12 lb.in 14 lb.in 18 lb.in