Buy ABB DDA202 AC-63/0.03 RCD Block, Type AC 2P 63A 30mA | Order By 1pm For Same Day Shipping
The ABB DDA202 AC-63/0.03 (alternate code 2CSB202001R1630) is a Type AC 2-pole 63A RCD block with 30mA residual current sensitivity, designed to add earth leakage protection when paired with compatible ABB S200 series miniature circuit breakers.
Part of ABB's trusted DDA200 product range, this RCD block provides protection against sinusoidal alternating earth fault currents and indirect contacts, while the 30mA sensitivity also delivers additional protection against direct contacts. It is an efficient solution for adding residual current protection to existing or new MCB installations without the need for a standalone RCCB, saving valuable DIN rail space in distribution boards.
Key Features
- Type AC Protection: Detects sinusoidal alternating earth fault currents, suitable for standard resistive and inductive loads.
- 63A Rated Current: Handles circuits up to 63 amps, making it ideal for higher-demand sub-circuits and distribution boards.
- 30mA Sensitivity: Provides additional protection against direct contact, meeting requirements for personal safety in most installations.
- 2-Pole Configuration: Compact design covering line and neutral, occupying minimal DIN rail space at just 69mm width.
- Wide Operating Temperature: Rated from −25°C to +55°C, suitable for both indoor and challenging ambient environments.
- 230V Rated Voltage: Designed for standard single-phase UK and European electrical systems.
- Lightweight and Compact: Weighing only 0.18 kg with dimensions of 93 × 69 × 70mm, it integrates easily into space-constrained enclosures.
- DIN Rail Mounting: Fits standard 35mm DIN rail via fast clip device for quick, secure installation.
Applications
The ABB DDA202 RCD block is used in residential, commercial, and industrial electrical installations where residual current protection must be added to S200 series MCBs. Typical applications include consumer units, sub-distribution boards, and final circuit protection for lighting, socket outlets, and fixed equipment. It is compliant with IEC/EN 61009 Annex G when assembled with an ABB S200 MCB, providing a combined RCBO-equivalent solution.
Standards and Compliance
Compliant with IEC/EN 61009 Annex G when combined with S200 MCBs; manufactured in Italy by ABB (order code 2CSB202001R1630).
Frequently Asked Questions
What MCBs is the ABB DDA202 RCD block compatible with?
The DDA200 range is designed to be assembled with ABB S200 series miniature circuit breakers, creating a combined unit that meets IEC/EN 61009 Annex G requirements.
What are the dimensions of the ABB DDA202 AC-63/0.03?
The unit measures 93mm (H) × 69mm (W) × 70mm (D) and weighs 0.18 kg.
Can this RCD block be used in cold environments?
Yes, it is rated for ambient temperatures from −25°C to +55°C, making it suitable for unheated plant rooms, outbuildings, and similar environments.
What is the difference between a DDA200 RCD block and a standalone F200 RCCB?
The DDA200 is an add-on block that clips directly onto an S200 MCB to provide combined overcurrent and earth leakage protection in a compact assembly, whereas the F200 is a standalone RCCB that requires a separate MCB upstream for overcurrent protection.
Where can I buy ABB DDA202 AC-63/0.03 RCD Block, Type AC 2P 63A 30mA 2CSB202001R1630 in the UK?
CSE Distributors, an official ABB franchised distributor with over 50 years' experience, supply this product from their branches in Wooburn Green and Southampton with same-day despatch available. They are highly rated with hundreds of positive customer reviews.
| Voltage | 230V |
|---|---|
| Number of Poles | 2 Pole |
| Product Range | DDA200 |
| Current Rating | 63A |
| Temperature Rating | -25 to +55°C |
| Residual Current | 30mA |
| Type | Type AC |
| Item Code | DDA202 AC-63/0.03 |
|---|---|
| Alternate Code | 2CSB202001R1630 |
| Manufacturer | ABB |
| Weight | 0.18 kg |
| Height | 93mm |
| Width | 69mm |
| Depth | 70mm |
| EAN | 8012542791300 |
| Commodity Code | 8536303000 |
| Country of Origin | Italy |