RT 2M Capillary Tube

RT Standard

Contact Type: SPDT
Contact material: Silver cadmium oxide
Loads: AC-1 ohmic 10A 400V
AC-3 (motor) 4A 400v
AC-15 (inductive) 3A 400V
Ambient Temperature -50 to 70°c

Type of Charge– with designation letters:
A: Vapour charge – sensor must not be the warmest part.
B: Adsorption charge
C: Partial charge – the sensor must not be the coldest part

OrderCode Type Type of Charge Set.Range°C Adjustable Diff at lowest range °C Adjustable Diff at Highest range °C Max Sensor Temperature°C
017-5066 RT9 A -45 > -15 2.2 > 10 1 > 4.5 150
017-5097 RT13 A -30 > 0 1.5 > 6 1 > 3 150
017-5014 RT3 A -25 > 15 2.8 > 10 1 > 4 150
017-5008 RT2 B -25 > 15 5 > 18 6 > 20 150
017-5053 RT7 B -25 > 15 2 > 10 2.5 > 14 150
017-5063 RT8 B -20 > 12 1.5 > 7 1.5 > 7 145
017-5089 RT12 B -5 > 10 1 > 3.5 1 > 3 65
017-5099 RT14 B -5 > 30 2 > 8 2 > 10 150
017-5180 RT26 B -5 > 50 2 > 9 3 > 19 150
017-5278 RT23 B 5 > 22 1.1 > 3 1 > 3 85
017-5115 RT15 B 8 > 32 1.6 > 8 1.6 > 8 150
017-5003 RT101 B 25 > 90 2.4 > 10 3.5 > 20 300
017-5048 RT106 C 20 > 90 4 > 20 2 > 7 120
017-5060 RT108 B 30 > 140 5 > 20 4 > 14 220
017-5135 RT107 C 70 > 150 6 > 25 1.8 > 8 215
017-5205 ^ RT120 C 120 > 215 7 > 30 1.8 > 9 260
017-5208 RT120 C 120 > 215 7 > 30 1.8 > 9 260
017-5220 RT123 C 150 > 250 6.5 > 30 1.8 >9 300
017-5227 RT124 C 200 > 300 5 > 25 2.5 > 10 350

^ Thermostats fitted with Neon lamp connected to terminal 4

RT Data Sheet