The Belden 5220UZ Multi Conductor data cable has a 16 AWG and ceramifiable silicone insulation, low smoke zero halogen sheath making it ideal for electrical circuits that need to maintain their integrity in the event of a fire – it has a 2 hour fire rating.
Cable Construction
| Number of Conductors: | 2 |
| Conductor AWG: | 16 |
| Conductor Stranding: | Solid |
| Conductor Material: | Bare Copper (BC) |
| Cable Insulation: | Flame Retardant Polyethylene (FRPE) |
| Nominal Wall Thickness: | 0.056″ |
| Cable Colouring: | Number 1: Black |
| Number 2 : Red | |
| Overall Nominal Diameter: | 0.350″ |
Mechanical Properties
| Operating Temperature Range: | -20°C To +105°C |
| UL Temperature Rating: | 105°C |
| Bulk Cable Weight: | 57 lbs/1000 ft. |
| Maximum Recommended Pulling Tension: | 62.5 lbs |
| Minimum Bending Radius (install) / Minor Axis: | 3.5″ |
| NEC/(UL) Specification: | FPLR, Electrical Circuit Protective Systems (FHIT #30) |
| NEC Articles: | 760 |
| EU CE Mark: | Yes |
| EU Directive 2000/53/EC (ELV): | Yes |
| EU Directive 2002/95/EC (RoHS): | Yes |
| EU RoHS Compliance Date: | 11/11/2005 |
| EU Directive 2002/96/EC (WEEE): | Yes |
| EU Directive 2003/11/EC (BFR): | Yes |
| CA Prop 65 (CJ for Wire & Cable): | Yes |
| MII Order #39 (China RoHS): | Yes |
| UL Flame Test: | UL1666 Riser, UL2196 Two Hour Circuit Integrity (in conduit only) |
| Plenum: | No |
Electrical Properties
| Nominal Capacitance Conductor to Conductor: | 15 pF/ft |
| Nominal Conductor DC Resistance at 20°C: | 4.0 |
| Maximum Operating Voltage – UL: | 300 V RMS |
UL 2196 (2 Hour Flame Rated) – Only when installed in conduit per FHIT #30 of the UL fire resistance directory.
Cable Ordering
| Order No. | Cable Length (ft) | Cable Weight (lb) | Colour | Description |
| 5220UZ 0021000 | 1,000 | 64 | Red | 2 #16 SIL FRNHPO |