Table 4E3B | Voltage Drop (per ampere per metre):Conductor Operating Temperature: 90°C

Voltage Drop (per ampere per metre):

Conductor Operating Temperature: 90oC

Conductor
cross-sectional
area
2 cables,
d.c.
Reference Methods C & F (clipped direct, on tray or free air)
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Touching Spaced* Trefoil and touching Flat and touching Flat and spaced*
1 2 3 4 5 6 7
(mm2) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)


r x z r x z r x z r x z r x z
50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.78 0.84 0.25 0.88 0.84 0.33 0.90
70 0.67 0.68 0.200 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70
95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58
120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.51
150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.45
185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41
240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37
300 0.155 0.170 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34
400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33
500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31
630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29
800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26
1,000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

Note:

* Spacings larger than one cable diameter will result in a larger voltage drop.