Medium Voltage Power Cable 3.3kV AWA

BS5467 & IEC60502-1 Cu/XLPE/PVC/AWA/PVC 1.9/3.3kV

Cu/XLPE/PVC/AWA/PVC mains power cable may be used for fixed installation indoors and outdoors in cable ducts or directly in the ground. The cable is XLPE insulated, PVC bedded, Aluminium Wire Armoured (AWA) and PVC sheathed with annealed copper conductors complying with BS6360 Class 2. 1900/3300 Volts to BS5467 the cable meets the requirements for flammability stated in IEC 60332-1 and BS EN 50265-2-1.

Construction characteristics

Conductor material: Copper
Conductor shape: Circular
Conductor flexibility: Stranded class 2
Insulation: XLPE (Cross-linked Polyethylene) - IEC60502
Inner sheath: PVC
Armour type: Aluminium wires
Outer sheath: PVC
Colour: Black
Lead free: Yes

Electrical characteristics

Rated Voltage Uo/U (Um): 1900/3300 Volts - BS5467

Usage characteristics

Minimum installation temperature: 0 °C
Maximum installation temperature: +60 °C
Installation type: Outdoor - Direct burial
Minimum operating temperature: -25 °C
Maximum operating temperature: 90 °C
Short-circuit max. conductor temperature: 250 °C
Flame retardant: IEC 60332-1
Bending radius: 6 x Overall diameter

Single Core: Brown inner & Black outer

Part Number Cross Section Stranding Approx Weight Approx Overall Diameter Gland Size Single Cleat Nom. Max. DC-resist conductor 20°C
(mm²) (mm) KG/KM (mm) (mm)
(Ohm/km)
3.3AWAPVC1X120 1 x 120 37/2.03 1490 23.2 25 1.2 0.153
3.3AWAPVC1X150 1 x 150 37/2.25 1870 26.3 32 1.2 0.124
3.3AWAPVC1X185 1 x 185 37/2.52 2290 28.7 32 1.4 0.0991
3.3AWAPVC1X240 1 x 240 61/2.25 2880 31.4 40 1.4 0.0754
3.3AWAPVC1X300 1 x 300 61/2.52 3520 34.1 40 1.8 0.0601
3.3AWAPVC1X400 1 x 400 61/2.85 4520 38.9 50s 1.8 0.0470
3.3AWAPVC1X500 1 x 500 61/3.2 5680 42.8 50s 1.8 0.0366
3.3AWAPVC1X630 1 x 630 127/2.52 7120 47.3 50 2.0 0.0283