CSE Cables supplies the Belden 1034A triad 300V power limited tray cable.
Belden 1034A Cable Construction
| Number of Conductor Triads: | 1 |
| Conductor AWG: | 16 |
| Conductor Stranding: | 7 x 24 |
| Conductor Material: | Bare Copper |
| Insulation Material: | F-R-PVC Flame retardant polyvinyl chloride |
| Inner Shield Colour: | Black and Red & White, Numbered (1) |
| Outer Shield: | Unshielded |
| Outer Jacket: | F-R PVC - Flame Retardant Polyvinyl Chloride |
| Outer Jacket Nominal Thickness: | 0.037" |
| Overall Cable Nominal Diameter: | 0.272" |
| Outer Jacket Ripcord: | Yes |
Mechanical Characteristics (overall)
| Operating Temperature Range: | -30°C To +105°C |
| Bulk Cable Weight: | 49.300 lbs/1000 ft. |
| Max. Recommended Pulling Tension: | 107 lbs. |
| Min. Bend Radius/Minor Axis: | 2.700 in. |
Electrical Characteristics (Overall)
| Nominal Conductor DC Resistance DCR @ 20°C: | 3.7 Ohm/1000 ft |
| Max. Operating Voltage UL | 300 V RMS |
Standards
| NEC/(UL) Specification: | CMG, ITC-ER, PLTC-ER |
| CEC/C(UL) Specification: | CMG |
| AWM Specification: | UL Style 2464 (300 V 80°C) |
| EU Directive 2011/65/EU (ROHS II) | |
| EU CE Mark | |
| EU Directive 2000/53/EC (ELV) | |
| EU Directive 2002/95/EC (RoHS) | |
| EU RoHS Compliance Date (mm/dd/yyyy) | 04/01/2005 |
| EU Directive 2002/96/EC (WEEE) | |
| EU Directive 2003/11/EC (BFR) | |
| CA Prop 65 (CJ for Wire & Cable) | |
| MII Order #39 (China RoHS) | |
| UL Flame Test: | UL1685 FT4 Loading |
| CSA Flame Test: | FT4 |
| IEEE Flame Test: | 1202 |
| Suitability - Burial: | Yes |
| Sunlight Resistance: | Yes |
| Plenum: | Yes |
Ordering Information
| Order Code | Reel Length (m) | Shipping Weight (kg) | Colour | Notes |
| 1034A 0101000 | 305 | 23.1 | Black | C |
| 1034A 0104000 | 1219 | 94.3 | Black | C Z |