Belden 3082A for DeviceNet

Belden 3082A Cable

The Belden 3082A data cable is a multi conductor, DeviceBus ® for ODVA DeviceNetTM.

Cable Construction

Cable Conductor 15AWG: 1 Pair, 19 x 28 stranding
Cable Conductor 18 AWG: 1 Pair, 19 x 30 stranding
Conductor Material: Tinned Copper (TC)
Insulation Material 15 AWG: Polyvinyl Chloride (PVC)
Insulation Material 18 AWG: Foam Polyethylene (FPE)
Inner Shield Material 15 AWG Pair: Aluminium Foil Polyester Tape 100% Coverage
Inner Shield Material 18 AWG Pair: Aluminium Foil Polyester Tape 100% Coverage
Outer Shield Material: Tinned Copper (TC) Braid 85% coverage
Outer Shield Drain Wire AWG: 18
Outer Shield Drain Wire Stranding: 19 x 30
Drain Wire Conductor: Tinned Copper
Outer Jacket Material: Polyvinyl Chloride (PVC)
Outer Jacket Thickness: 1.524mm
Overall Nominal Diameter: 12.192mm
1 (15 AWG) Pair Colour: Red and Black
2 (18 AWG) Pair Colour: Blue & White

Mechanical Properties

Operating Temperature Range: -20°C to +75°C
UL Temperature Rating: 75°C
Bulk Cable Weight: 160.726 Kg/Km
Max. Recommended Pulling Tension: 845.158 N
Min. Bend Radius/Minor Axis: 121.920 mm
NEC/(UL) Specification: CMG, PLTC-ER
CEC/C(UL) Specification: CMG
AWM Specification: UL Style 20201 (600 V 75°C)
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Other Specification: ODVA Class 2 Thick
UL Flame Test: UL1685 FT4 Loading
CSA Flame Test: FT4
Sunlight Resistance: Yes
Oil Resistance: Yes
Plenum: No

Electrical Characteristics

Unaveraged Impedance 18 AWG Pair: 120 Ohm
Nominal Inductance 15 AWG Pair: 0.570894 μH/m
Nominal Capacitance Conductor to Conductor 18 AWG Pair: 1 MHz / 39.372 pF/m
Nominal Velocity of Propagation 18 AWG Pair: 75%
Maximum Delay 18 AWG Pair: 4.46216 ns/m
Nominal Conductor DC Resistance 15 AWG @ 20°C: 11.8116 Ohm / km
Nominal Conductor DC Resistance 18 AWG @ 20°C: 22.6389 Ohm / km
Nominal Outer Shield DC Resistance @ 20°C: 5.9058 Ohm / km
Maximum Attenuation 0.42653 (18 AWG Pair): 0.125 MHz / 0.427 dB/100m
Maximum Attenuation 0.82025 : 0.5 MHz / 0.820 dB/100m
Maximum Attenuation 1.3124 : 1 MHz / 1.181 dB/100m
Maximum Operating Voltage : 300 V RMS (CL2,CMG)
600 V RMS (UL AWM Style 20201)
300 V RMS (C(UL) AWM)
Maximum Recommended Current 15 AWG : 8.0 Amps
Maximum Recommended Current 18 AWG : 5.0 Amps

Meter marks on jacket to aid users in installation. ODVA DeviceNet is an Open DeviceNet Vendor Associatio, Inc. Trademark. Jacket printed "1PR16" instead of
"1PR15" due to UL requirements for CMG Listing.


Cable Ordering Information

Cable ID Cable Length m Weight kg Colour Item Description
3082A T5U2000 610 122 Grey T5U 2 #15, 2 #18 SHLD PVC
3082A T5U3000 914 193 Grey T5U 2 #15, 2 #18 SHLD PVC
3082A T5U500 152 31 Grey T5U 2 #15, 2 #18 SH PVC