The Belden 3107A paired EIA industrial RS-485 PLTC/CM cable is a 22 AWG stranded (7 x 30) tinned copper conductor UV resistant data cable.
Cable Construction
| Number of Pairs: | 2 |
| Total Number of Conductors: | 4 |
| Conductor AWG: | 22 |
| Conductor Stranding: | 7 x 30 |
| Conductor Diameter: | 0.762mm |
| Conductor Material: | Tinned Copper (TC) |
| Insulation Material: | Datalene ® Foam High Density Polyethylene (FHDPE) |
| Overall Cabling Colour Code: | 1: White / Blue Stripe & Blue / White Stripe |
| 2: White / Orange Stripe & Orange / White Stripe | |
| Outer Shield Material: | Beldfoil ® Tape / Braid |
| Outer Shield Coverage: | 100% |
| Outer Shield Drain Wire AWG: | 22 |
| Outer Shield Drain Wire Stranding: | 7 x 30 |
| Outer Shield Drain Wire Diameter: | 0.762 mm |
| Outer Shield Drain Wire Conductor Material: | Tinned Copper (TC) |
| Outer Jacket Material: | Polyvinyl Chloride (PVC) |
| Overall Nominal Diameter: | 9.042mm |
Mechanical Properties
| Operating Temperature Range: | -20°C To +60°C |
| Non-UL Temperature Rating: | 60°C |
| Bulk Cable Weight: | 108.639 Kg/Km |
| Max. Recommended Pulling Tension: | 355.856 N |
| Min. Bend Radius (Install): | 91.44 mm |
| NEC/(UL) Specification: | CM, PLTC OIL RES II |
| CEC/C(UL) Specification: | CM |
| EU CE Mark: | Yes |
| EU RoHS Compliant: | Yes |
| EU RoHS Compliance Date (mm/dd/yyyy): | 10/01/2005 |
| UL Flame Test: | UL1685 UL Loading |
| CSA Flame Test: | FT1 |
| Sunlight Resistance: | Passes UL 1581, 720 Hours |
| Plenum: | No |
| Input/Unfitted Impedance Frequency: | 1 |
| Nominal Characteristic Impedance: | 120 Ohms |
| Nom. Capacitance Conductor to Conductor @ 1 KHz: | 36.091 pF/m |
| Nom. Cap. Cond. to Other Cond. & Shield @ 1 KHz: | 68.573 pF/m |
| Nominal Velocity of Propagation: | 78% |
| Nom. Conductor DC Resistance @ 20 Deg. C: | 48.231 Ohms / km |
| Nominal Outer Shield DC Resistance @ 20 Deg. C: | 5.906 Ohms/km |
| Nom. Attenuation (dB/100 ft) : | 1 MHz 1.64 dB / 100m |
| Max. Operating Voltage - UL: | 300 V RMS |
| Max. Recommended Current: | 2.7 Amps per conductor @ 25°C |
Oil Resistance: Passes Oil Res II Per UL1277, Table 10.17. For CPE jacketed version order YR46792
Belden 3107A Paired Ordering Information
| Order No. | Description | Cable Length (m) | Shipping Weight (kgs) | Sheath Colour |
| 3107A 0101000 | 2 PR #22 FHDPE SH PVC | 304.8 | 31.326 | Black |
| 3107A 0104000 | 2 PR #22 FHDPE SH PVC | 1219.2 | 136.2 | Black |
| 3107A 0105000 | 2 PR #22 FHDPE SH PVC | 1524 | 174.79 | Black |
Final cut length may vary ±10% from length shown.